List of messages
Display messages
36 05/2020, 4BS0576F-004
Msg-
Number
Display line 1
Display line 2
Text for event memory entry
Fault sup-
pression on
Description
3463 !! Emergency stop !! Contr. AD missing ESt>contr. AD - As message no. 3453,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=Emergency stop" parameterized
3464 !! Emergency stop !! Interruption RS485 ESt>InterrptRS485 - As message no. 3454,
at "P-INTERFACES/P-RS485/Rct.RS485=Emergency stop" parameterized
3465 !! Emergency stop !! Interr. RS485 (X26) ESt>Int.RS485 X26 As message no. 3455,
at "P-INTERFACES/P-RS485/Rct.RS485=Emergency stop" parameterized
3471 !! OFF 1 !! Interruption BUS OFF1>Interrpt.BUS - As message no. 3451,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=OFF1" parameterized
3472 !! OFF 1 !! BUS Hardware OFF1>BUS Hardware - As message no. 3452,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=OFF1" parameterized
3473 !! OFF 1 !! Contr. AD missing OFF1>contr. AD - As message no. 3453,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=OFF1" parameterized
3474 !! OFF 1 !! Interruption RS485 OFF2>Interrpt.BUS - As message no. 3454,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=OFF1" parameterized
3475 !! OFF 1 !! Interr. RS485 (X26) OFF2>InterrpRS485 As message no. 3455,
at "P-INTERFACES/P-Fieldbus/Rct.BUS=OFF1" parameterized
3600 Controller release missing A run command is active; however, the controller is not released. Connect
the controller release to –X2:8 (or if not available, insert a jumper) check
parameter "P-OPERATION/P-ContrlRelease", which act on additional
inputs for controller release. Then also check these inputs.
3601 Sensor adjustm. in process - Presently, an "automatic" sensor adjustment is carried out. Wait for the
sensor adjustment.
3602 Auto-Tuning in process - In this connection, the inverter measures the connected motor and opti-
mizes automatically its motor parameter.
3603 Sensor adjustm. faulty - The "automatic" sensor adjustment cannot be carried out successfully.
Carry out "P-motor data/Sensor adjustm." again or set
"P-motor data/Sensor offset" manually.
3604 Auto-Tuning faulty - Auto-tuning cannot be carried out automatically. Connect the motor cor-
rectly to the inverter and carry out Auto-tuning again. Simple speed con-
trols, e.g. for pumps or ventilators may work perfectly even without Auto-
tuning. If there is a problem, contact out service station.
3605 Sensor adjustm. no contr. Release - Tue automatic sensor adjustment could not be carried out as the controller
release is missing. Remedy: perform "P-
motor data/Sensor adjustm." again
or set "P-motor data/Sensor offset" manually.
3606 Fault Write errror EEPROM - Fault upon parameterizing: Correct writing on EEPROM was not possible;
repeat the parameterizing.