3607 Terminal X2:8 inactive - There is no ON-command parameterized to terminal -X2:8. At terminal
-X2:8 however, there is inverter-internal a cutoff by hardware always avail-
able. Bridge terminal -X2:8 or set an ON-command on this terminal.
3608 Main contactor off - Normal operational status: the inverter is switched off, thus, also the main
contactor is disconnected.
Normally the inverter will start upon the next ON-command.
3609 Contactor feedback missing - The inverter needs a feedback contact of the main contactor. The make
contact must be connected to that terminal, which is parameterized under
"P-OPERATION/Feedb.MC".
3610 Mains voltage faulty - The inverter is equipped with a main contactor function. Upon inverter start
the contactor operates. The acknowledgement goes back to the inverter.
The line voltage monitoring is getting active and recognizes a mains failure.
Recheck all phases of the line voltage before the main contactor;
Maybe check also the circuit of the main contactor drive: does the main
contactor engage yet before the mains are connected?
3611 Store Factory param - Message that appears only on first inverter initialization.
3612 Input power failure active - The input that locks all inputs in case of a line voltage failure (with the
effect that no undesired fault messages are appearing) is active.Recheck
the control voltage; recheck the input circuit parameterized at
"P-OPERATION/MainsFlt". Here, only a relay/voltage measuring relay
should be connected, to monitor the control voltage.
3615 !! OFF 2 !! After STO act. - The safe torque off command was again set to GOOD. This message
indicates that the inverter remains in the OFF 2 state, and despite the ON
commands entered, it does not automatically restart. You can exit OFF 2
with a reset or an OFF 1. If you wish that, after a "Safe torque off" with an
ON command the inverter automatically restarts,
then you must switch over
parameter, "P-INVERTER DATA/P-Monitoring/STO" from
"Store" to "Auto.reset".
3616 Safe torque off active - Via terminals X2:19/:20, currently the "Safe torque off" function is initiated.
3617 Wait test STO X2:8 inactive - You have manually activated the test of the two switch-off signal paths for
the "Safe torque off" function using parameter "P-EXTRAS/Test
STO/PTC". The test cannot be performed as long as terminal -X2:8 is
deenergized. The inverter waits to perform the test until the terminal is
energized. Jumper terminal -X2:8, or issue an appropriate on command.