List of messages
Display messages
38 05/2020, 4BS0576F-004
Msg-
Number
Display line 1
Display line 2
Text for event memory entry
Fault sup-
pression on
Description
3618 Wait test STO Main contactor off - You have manually activated the test of the two switch-off signal paths for
the "Safe torque off" function using parameter "P-EXTRAS/Test
STO/PTC". The test cannot be performed as long as a line contactor has
not been closed. The inverter waits to perform the test until the line con-
tactor has closed. Check the circuit of the main contactor coil and that of
the feedback signal contact. Check the parameterization of the main con-
tactor function under "P-OPERATION/Feedb.MC" and "P-INV.
BEHAVIOUR/MCfunc".
3619 Test safe torque off in process - Presently, the internal plausibility test for the safe halt is running (max. 5s)
Wait for the test result.
3620 Test PTC X3:90/91 in process - Presently, the internal plausibility test for the electronic cutoff path for the
thermistor is running (max. 5s). Wait for the test result.
3621 !! OFF 1 !! Operation - Command OFF1 is active.
You can check under "P-OPERATION/P-OFF1(NC)", which input is re-
sponsible for this cutoff.
3623 Download Parameter active This
message occurs if parameters are downloaded from IMS to inverter. If
this message is not gone automatically after some minutes, please start
the download again.
3625 Mains synchronization completed Only in Control mode mains synchronization: Information, that mains syn-
chronization is successful finished
3633 Vlt. Sig.Brd. nOK The 24V-feed in of the signals board -A13 is not ok. Check the 24V-feed in
at the terminals -A13-X7:1 and :2(M)
3700 Software fault Use old software version and contact our service station.
3701 no inverter off ! Stop inverter with control release, e.g. for parameterization
3702 not possible ! This message occurs only via interface, when wrong parameters indicated.
Please use only correct parameters.
3703 Para. protected ! It is not possible to change parameters because of the parameter protec-
tion. Please deactivate the parameter protection.
3704 Write errror EEPROM Cancel the last changings and contact our service station.
3705 Read error EEPROM Cancel the last changings and contact our service station.
3706 Write errror RTC Cancel the last changings and contact our service station.
3707 Read error RTC Cancel the last changings and contact our service station.
3708 RAM-fault! Cancel the last changings and contact our service station.
3709 Illegal value! This message occurs only via interface, when wrong parameters indicated.
Please use only correct parameters.
3710 Omniscience fault! Cancel the last changings and contact our service station.