EasyManua.ls Logo

Siemens SINUMERIK 840D sl Ctrl-Energy

Siemens SINUMERIK  840D sl Ctrl-Energy
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Data block for auxiliary systems
Up to 10 auxiliary systems are supported by the data block. A data structure is defined for each
auxiliary system. In order to display the energy/power of an auxiliary system in the HMI, bit 0
of the first byte of the data structure must be set.
Auxiliary system Start of the data structure End of the data structure
Auxiliary system 1 (n=0) DB9907.DBB100 DB9907.DBB139
Auxiliary system 2 (n=40) DB9907.DBB140 DB9907.DBB179
Auxiliary system 3 (n=80) DB9907.DBB180 DB9907.DBB219
Auxiliary system 4 (n=120) DB9907.DBB220 DB9907.DBB259
Auxiliary system 5 (n=160) DB9907.DBB260 DB9907.DBB299
Auxiliary system 6 (n=200) DB9907.DBB300 DB9907.DBB339
Auxiliary system 7 (n=240) DB9907.DBB340 DB9907.DBB379
Auxiliary system 8 (n=280) DB9907.DBB380 DB9907.DBB419
Auxiliary system 9 (n=320) DB9907.DBB420 DB9907.DBB459
Auxiliary system 10 (n=360) DB9907.DBB460 DB9907.DBB499
DB9907
Name: SentronPac
Signal
direction
Meaning Identifier Format
DB9907.DBX(100+n).0 PLC ->
FW/HMI
FW calculates the energy/
power of the auxiliary sys‐
tem
ProcessAux BOOL
DB9907.DBX(100+n).1 PLC ->
FW/HMI
Actual value update ReadEnergy BOOL
DB9907.DBX(100+n).2 PLC ->
FW/HMI
Measurement in progress MeasACT BOOL
DB9907.DBX(100+n).3 PLC ->
FW/HMI
1: Differential values are
written to the variables for
the measurement end
0: Absolute values are
written to the variables for
the measurement start
and measurement end
MeasMode BOOL
DB9907.DBX(100+n).4 PLC ->
FW/HMI
1: Energy
0: Power
InputMode BOOL
DB9907.DBX(100+n).7 PLC ->
FW/HMI
Delete data structure ResetAux BOOL
DB9907.DBD(104+n) PLC ->
FW/HMI
Active power or active en‐
ergy of the auxiliary sys‐
tem
ActivePowerAux REAL
DB9907.DBD(108+n) FW ->
HMI
Active energy drawn by
the auxiliary system in
kWh
ActiveEnAux REAL
DB9907.DBD(112+n) FW ->
HMI
Active energy supplied by
the auxiliary system in
kWh
ReActiveEnAux REAL
Ctrl-E Analysis
3.3 Commissioning the PLC for Ctrl-E Analysis
Ctrl-Energy
32 System Manual, 01/2015, 6FC5397-0EP40-5BA2

Table of Contents

Related product manuals