Application Planning
4.1 Secondary electrical conditions
NCU 7x0.2
30 Manual, 02/2011, 6FC5397-0AP20-0BA0
4.1.2 RI suppression measures
In addition to the protective grounding of system components, special precautions must be
taken to ensure safe, fault-free operation of the system. These measures include shielded
signal lines, special equipotential bonding connections, and isolation and shielding
measures.
Shielded signal lines
For safe and smooth operation of the system, the specified cables must be used. Please
refer to the chapter titled Connection.
For digital signal transmission, the shield must have a conductive connection at both
sides of the housing.
Cable definitions
Signal cables (example)
Data cables (Ethernet, PROFIBUS, PROFINET, sensor cables, etc.)
Digital inputs/outputs
EMERGENCY OFF lines
Power cables (example)
Supply voltage 1 x 230 V AC or 3 x 400 V AC
Motor cables
Rules for routing cables
In order to maximize noise immunity for the complete system (controller, power section,
machine) the following EMC measures must be observed:
A minimum distance of 200 mm is to be observed between the signal lines and power
cables.
If necessary, signal and load cables may cross one another (if possible, at an angle of
90°), but must never be laid close or parallel to one another.
Only use cables approved by Siemens for the signal lines from and to the Control Unit.