To calculate the heat dissipation, the total power loss P
Vtotal
of all heat-generating components
in a housing must be taken into account.
Total power loss P
Vtotal
= P
V1
+ P
V2
+ P
V3
+... [W]
Convection surface area A [m
2
]:
The surface areas of the front and bottom sides are not included in the convection surface
area calculation.
Note
A recommended value for the power loss of the operator control components is contained in the
"Technical data" section of the associated component (see "Power consumption").
Means of heat dissipation
Heat dissipation can take place as follows:
Heat dissipation by natural convection
Heat dissipation by natural convection and internal air turbulence
Heat dissipation by open-circuit cooling
Heat dissipation by open-circuit ventilation
General information and networking
4.1Application planning
Handheld Terminal HT 8
Equipment Manual, 02/2024, A5E52918633B AA 29

Table of Contents

Other manuals for Siemens SINUMERIK ONE MCP 2400.4c

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK ONE MCP 2400.4c and is the answer not in the manual?

Siemens SINUMERIK ONE MCP 2400.4c Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK ONE MCP 2400.4c
CategoryControl Systems
LanguageEnglish

Related product manuals