Auxiliary switch (-S1)
Power consumption
Breaking capacity
The auxiliary switch (-S1) is available for delivery in two
versions: With 6 NO contacts or 12 NC contacts each.
Contacts available on the customer's premises - see cir-
cuit diagram supplied.
Fig. 28 Auxiliary switch (31)
Rated insulation voltage: 250 V AC/DC
Insulation group: C as per VDE 0110
Continuous current: 10 A
Closing capacity: 50 A
Rated operating voltage Rated normal current
up to U (V) I (A)
Ohmic
load
Inductive load
(T = 20 ms)
230 AC 10 10
24 DC 10 10
48 DC 10 9
60 DC 9 7
110 DC 5 4
220 DC 2.5 2