EasyManua.ls Logo

Siemens SION 3AE5 - Reuse of Transport Unit; Storage

Siemens SION 3AE5
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Transport, storage and packing
10 9229 0025 176 0A
2019-08-05
Reuse of transport unit
Reusing the transport unit The transport pallet and the carton as well as most of the components can be reused
if the vacuum circuit-breaker is to be transported again.
Do not reuse severed tensioning belts or plastic strapping.
Pack the vacuum circuit-breaker in reverse order:
Secure the vacuum circuit-breaker safely on the transport pallet with suitable
aids.
Cover with film and seal with adhesive tape.
Attach supplementary equipment.
Close carton securely.
Before returning to the factory, ask the responsible Siemens representative for a
returned products number (see also “Service”, on page 63).
When returning a vacuum circuit-breaker, always specify the type and serial
number (see “Name plate”, on page 31).
Storage
Store the vacuum circuit-breaker in the following condition:
OPEN switch position
Closing spring discharged
Note
Risk of corrosion damage if stored improperly!
Failure to observe the storage conditions shortens the storage life and the vacu-
um circuit-breaker may be damaged.
If the storage conditions listed below are met, the vacuum circuit-breaker can
be stored for up to a year in its transport unit.
If the storage conditions are not met, the vacuum circuit-breaker cannot be
stored in the transport unit for longer than 6 months.
If storage for more than one year is planned, unpack the vacuum circuit-
breaker from the transport unit. Further storage may necessitate fresh corro-
sion protection, and it must be ensured that the vacuum circuit-breaker can-
not be damaged.
Storage room Transport unit Storage
time
Temperature
range
Comment Number of
units per
stack
Enclosed, dry, well
ventilated, and as
free from dust as
possible, with a rela-
tive air humidity
below 60 %.
Unopened
max.
6months
-4C to +5C
-4F to 13F
—max. 4
Unopened
max.
1year
-5 °C to +40 °C
23 °F to 104 °F
—max. 4
Open
More than
1year
-5 °C to +40 °C
23 °F to 104 °F
with new corro-
sion protection if
necessary

Related product manuals