Ambient conditions
Occasional condensation may occur under these ambient conditions.
SION
®
 vacuum circuit-breaker are suitable for use in the following climate classes
according to IEC 60721, part 3-3:
Installation altitudes
Dielectric strength The dielectric strength of insulation in air declines with rising altitude due to the lower
air density. As per IEC 62271-1, the rated lightning impulse withstand voltage values
given in Fig. 43 are valid up to an installation altitude of 1000 m above sea level. 
Above an altitude of 1000 m, the insulation level must be corrected as shown in
Fig. 45:
Class
• Climatic ambient conditions:
3K4
1)
• Biological ambient conditions: 3B1
• Mechanical ambient conditions: 3M2
• Chemically active substances:
3C2
2)
3C3
3)
• Mechanically active substances:
3S2
4)
1) Minimum temperature limit: -5 °C / 23 °F (with addition A40 to 
-25 °C / -13 °F)
2) Without occurrence of salt fog and simultaneous condensation
3) Class 3C3 (H2S < 20 ppm in dry air < 50 % with order code 
D20)
4) Restriction: Clean insulation parts
5) Average value, measured over 24 hours
6) Average value, measured over 1 month
Fig. 44 Ambient conditions
+55 °C
131 °F
-5 °C 
1)
23 °F 
1)
95 % 
5)
90 % 
6)
5%
U  ≥ U
0
  K
a
U Rated withstand voltage U under standard reference 
atmosphere
U
0
Required rated withstand voltage for the installation 
location
K
a
Altitude correction factor
K
a
 = e
m
 
 (H - 1000)/8150
Calculating the altitude correction factor K
a
:
H = Site altitude in metres
m = 1 for AC voltage, lightning impulse withstand volt-
age (between phases, phase-ground, applied lon-
gitudinally)
Example
For a required rated withstand voltage of 75 kV at an al-
titude of 2500 m, an insulation level of at least 90 kV un-
der standard reference atmosphere conditions is
required:
90 kV ≥ 75 kV  e
1
  
(2500 - 1000)/8150
≈75 kV  1.2
Fig. 45 Altitude correction factor K