EasyManua.ls Logo

Siemens SION 3AE5 - Mounting contact arms and systems

Siemens SION 3AE5
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
9229 0025 176 0A 51
2019-08-05
When tightening the screws, hold the nuts against the tightening torque with a suit-
able screwdriver or socket spanner.
Tightening torque for
- M12: 40 ±4 Nm
- M16: 100 ±10 Nm
Tightening torques apply to greased threads only.
Securing with a spiral
spring pin
The conductor bars can be secured against twisting with a spiral spring pin accord-
ing to ISO 8748 or a dowel pin according to ISO 8752 — 4 × X*
)
mm — N — C.
A drill hole Ø 4H11 must be provided in the conductor bar (see Fig 81, horizontal ar-
row).
See dimension drawings.
*
)
X = Length of the spring pin, depending on the cross-section of the busbar in mm
Mounting contact arms and systems
Grease the screw-in section of the threaded rods with Vaseline.
Screw in the threaded rod and observe the screw-in depths for safe use (see
Table “Screw-in depths from contact surface in the upper and lower terminals”,
page 50).
Screw the threaded rods to the contact surfaces.
Tightening torque for
- M12: 40 ±4 Nm
- M16: 100 ±10 Nm
Tightening torques apply to greased threads only.
End faces of the copper contact arms must be
- roughened, cleaned and
- greased with Vaseline.
End faces with silver-plated contact surfaces must be
- cleaned and
- greased with Vaseline.
Fig. 82 Cleaning and mounting threaded rods (22.1)
for contact arms (22)
Fig. 83 Cleaning and mounting contact arms (22)

Related product manuals