Description
26 9229 0025 176 0E
2021-11-15
Auxiliary switch (-S1)
Power consumption
Breaking capacity
The auxiliary switch (-S1) is available for delivery in two
versions: with 6 NO contacts or 12 NC contacts each.
Contacts available on the customer’s premises – see cir-
cuit diagram supplied.
Fig. 26 Auxiliary switch (31)
Rated insulation voltage: AC/DC 250 V
Insulation group: C as per VDE 0110
Continuous current: 10 A
Closing capacity: 50 A
Rated operating voltage Rated normal current
up to U (V) I (A)
Ohmic
load
Inductive load
(T = 20 ms)
AC 230 10 10
DC 24 10 10
DC 48 10 9
DC 60 9 7
DC 110 5 4
DC 220 2.5 2