EasyManua.ls Logo

Siemens SION - Key Technical Specifications

Siemens SION
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description
34 9229 0025 176 0E
2021-11-15
Name plate
Technical data
Vacuum circuit-breaker SION
®
Fig. 41 Technical specifications, SION
®
vacuum circuit-breaker
Fig. 40 Example – name plate
1) Manufacturer
2) Type designation
3) Factory number
4) Rated voltage U
r
5) Rated frequency f
r
6) Rated short-circuit breaking current I
sc
7 Rated power frequency withstand
voltage U
d
8) Rated lightning impulse withstand
voltage U
p
9) Year of manufacture
10) Rated normal current I
r
11) Rated short-circuit duration t
k
12) Mass m
13) Rated operating sequence
14) Classification E2, C2 and M2 for circuit-
breakers according to the standard
Type: 3AE5656-6
No.: S 3AE5/90000508
Year of manufacture
2021
U
r
17.5 kV 50/60 Hz I
r
2500 A
I
sc
40 kA t
k
3s
U
d
/U
p
42 kV/ 95 kV
m
140 kg
Rated operating sequence: O–0.3 s–CO–15 s–CO
Class as per IEC 62271-100: E2, C2 and M2
Made in Germany
1)
2)
3)
4), 5)
6)
7), 8)
9)
10)
11)
12)
13)
14)
Rated voltage U
r
(at f
r
50/60 Hz)
kV 7.2 12 17.5 24
Rated normal current I
r
A
800 – 3150
b)
/ 4000
fc
c)
800 – 2500
Rated lightning impulse withstand voltage (peak value)
U
p
kV 60
75 (95
a)
)
95 125
Rated short-duration power frequency withstand voltage
(RMS) U
d
kV
20 (32
a)
)28 (42
a)
)
38
50 (65
a)
)
Rated short-circuit breaking current I
sc
kA 16 – 40 16 – 25
Pole-centre distance mm 150, 160, 210, 275 210, 275
Distance between lower and upper terminal mm 205, 275, 310 310
Standard rated operating sequence O – 0.3 s – CO – 15 s – CO
a) On request
b) From 2000 A upwards only with 310 mm space between the lower and the upper terminal
and a pole-centre distance of 210/275 mm
c) only with additional active cooling (fc)