Transport, storage and packing
9229 0025 176 0E 13
2021-11-15
Reuse of transport unit
Reusing the transport unit The transport pallet and the box, as well as most of the components, can be reused
if the vacuum circuit-breaker is to be transported again.
Do not reuse severed tensioning belts or plastic wraps.
Pack the vacuum circuit-breaker in reverse order:
Secure the vacuum circuit-breaker safely on the transport pallet with suitable
aids.
Cover with PE film and seal with adhesive tape.
Attach the supplementary equipment.
Close the box securely.
Before returning to the factory, ask the responsible Siemens representative for a
returned products number (see also “Service”on page 2).
When returning a vacuum circuit-breaker, always specify the type and serial
number (see “Name plate”, on page 34).
Storage
Store the vacuum circuit-breaker in the following condition:
Risk of corrosion damage if stored improperly!
Failure to observe the storage conditions shortens the storage life and the vacuum
circuit-breaker may be damaged.
If the storage conditions listed below are met, the vacuum circuit-breaker can be
stored for up to a year in its transport unit.
If the storage conditions are not met, the vacuum circuit-breaker cannot be
stored in the transport unit for longer than 6 months.
If storage for more than one year is planned, unpack the vacuum circuit-breaker
from the transport unit. Further storage may necessitate fresh corrosion protec-
tion, and it must be ensured that the vacuum circuit-breaker cannot be dam-
aged.
OPEN switch position
Closing spring discharged
Note
Storage room Transport unit Storage
time
Temperature
range
Comment Number of
units per
stack
Enclosed, dry, well
ventilated, and as
free from dust as
possible, with a rela-
tive air humidity
below 60 %.
Unopened
max.
6months
-40 °C to +55 °C
-40 °F to 131 °F
max. 4
Unopened
max.
1 year
-5 °C to +40 °C
23 °F to 104 °F
max. 4
Open
More than
1 year
-5 °C to +40 °C
23 °F to 104 °F
with new corro-
sion protection if
necessary