Installation
9229 0025 176 0E 55
2021-11-15
A drill hole Ø 4H11 must be provided in the conductor bar (see Fig. 83, horizontal
arrow).
See dimension drawings.
*
)
X = Length of the spring pin, depending on the cross-section of the conductor bar in mm
Contact arms and systems
Two versions of contacts (contact arms and systems) are available for SION
®
vac-
uum circuit-breakers, each designed for different types of switchgear:
Siemens contacts
Third-party contacts
The two versions differ in terms of their construction and assembly, so that a distinc-
tion is made between the two versions below where it is technically relevant.
Mounting Siemens contacts
Grease the screw-in section of the threaded rods (22.1) with Vaseline (see 1.).
Screw in the threaded rod (22.1) and observe the screw-in depths A+B (see 2.)
(see TableScrew-in depths for screws or threaded rods from the contact sur-
face in the upper and lower connection”, page 54).
Tighten the threaded rods (22.1) on the contact surfaces of the upper and lower
connections (see 3.)
Tightening torques for greased threads:
- M12: 40 ±4 Nm
- M16: 100 ±10 Nm
Fig. 84 Cleaning and mounting threaded rods (22.1)
for contact arms (22)
Fig. 85 Cleaning and mounting contact arms (22)
0025-68
22.1
A
B
1.
2.
0025-69
22.1
22
4.
3.
Contact surfaces, Copper, silver-plated
- roughen x
- clean, x x
- grease with Vaseline (see 4.) x x