Installation
9229 0025 176 0E 63
2021-11-15
Place the contact system on a surface so that the openings of the contact sys-
tem are not covered.
A device for centring the contact system may be required.
Position the inner part (metal body) of the contact system over the opening with
the narrower side facing inwards (see 1.).
Press the inner part (metal body) of the contact system through the contact fin-
gers (see 2.) until the rear part of the contact fingers is in the groove (see 3.).
Grease the contact fingers with Molykote Longterm 2 on the inside (round outer
edge) of the contact system (see 4.).
Mount the contact system on the threaded rod and contact arm, paying attention
to the position of the contact system in relation to the contact arm (see 5.).
Tightening torque applies to greased threads only
- M12: 40 ±4 Nm
- M16: 100 ±10 Nm
Grease contact fingers of the contact system with Molykote Longterm 2.
Function test After completing all work on the vacuum circuit-breaker, perform a function test in
accordance with “Commissioning”, p. 69.
Fig. 106 Installation of the contact systems on the con-
tact arms
M12: 40 ±4 Nm
M16: 100 ±10 Nm