EasyManua.ls Logo

Siemens SION - Page 65

Siemens SION
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
9229 0025 176 0E 65
2021-11-15
Position queries during movement
If the low-voltage interface has been connected on the customer’s premises, the fol-
lowing positions of the vacuum circuit-breaker with withdrawable part are sensed
during movement:
Manually moving the SION
®
vacuum circuit-breaker on the withdrawable part
Requirement: Vacuum circuit-breaker is open and switch position OPEN is dis-
played.
Withdrawable part in entry
position
Insert hand crank into the coupling of the withdrawable part
Turn inserted hand crank of withdrawable part clockwise in order to move the
vacuum circuit-breaker to a perceivable end stop
Remove the hand crank withdrawable part from the coupling of the withdrawa-
ble part
Withdrawable part in
service position
Insert hand crank into the coupling of the withdrawable part
Turn inserted hand crank anti-clockwise in order to move the vacuum circuit-
breaker into the service position to a perceivable stop
Remove hand crank from the coupling of the withdrawable part
Disconnected position / test position Intermediate position Retracted position / service position
Buttons –S1.5; –S1.6; –S1.7; –S1.8
send a signal or message
No signal Buttons –S1.0; –S1.1; –S1.2; –S1.3 send
a signal or message
Fig. 109 Example – moving in the guide rails