3 Operation
3.3 Configuring Mode (Parameterization and Configuring Mode)
3.3.3 Configuring Mode oFPA (Offline Parameters)
SIP ART DR24 6DR2410
C79000-G7476-C153-03
147
dd2 dd3 dd1
Setting range
Fac-
tory
setting
Resolu-
tion
Di-
men-
sion
Parameter meaning
dA2.1
1)
dA2.2
dA
dE
dA
dE
--199.9 to 199.9
0.0
100.0
0.0
100.0
0.1
%
Analog display 2 Input 1 Start of scale
Full scale Signal
Analog display 2 Input 2 Start of scale range
Full scale
dA2.3
1)
dA2.4
dA
dE
dA
dE
--199.9 to 199.9
0.0
100.0
0.0
100.0
0.1
%
Analog display 2 Input 3 Start of scale
Full scale Signal
Analog display 2Input 4 Start of scale range
Full scale
FUL1 0 0.0 Function transmitter 1 (linear), vertex at 0 %
↓
20 20,0 20 %
FUL2 40
40.0
Function transmitter 2 (linear) 40 %
↓
60
--199.9 to 199.9
60.0
0.1 %
60 %
FUL3 80 80.0 Function transmitter 3 (linear) 80 %
100 100.0 100 %
--10 -10,0 Function transmitter 1 (parabola), vertex at --10 %
FUP1 0 0.0 0%
10 10.0 10 %
↓
20 20.0 20 %
FUP2 30 30.0 30 %
40 40.0 Function transmitter 2 (parabola) 40 %
50
--199.9 to 199.9
50.0
0.1 %
50 %
60 60.0 60 %
70 70.0 70 %
80 80.0 80 %
90 90.0 90 %
100 100.0 100 %
110 110.0 110 %
MUP1
Multiplexer 1
MUP2
t
2to8 8 1 -
2
steps
SES
2)
bdr
300
600
1200
2400
4800
9600
9600
-- baud
Serial interface
baud rate (transmission speed)
Lrc
norM
CMPL
norM
-- --
Longitudinal parity formation ETX normal
complement
LEt
no L
Et--L
L--Et
no L
-- --
Longitudinal parity position without Lrc
with Lrc after ETX
with LRC before ETX
Prt
EvEn
odd
EvEn
-- --
vertical parity formation even
odd
Snr 0to125 0
-- --
Station number
Cbt OFF
1
2
3
4
5
7
10
15
20
30
oFF
--
--
--
--
--
--
--
--
--
--
--
--
s
s
s
s
s
s
s
s
s
s
CB watchdog on SbE1
High speeed steps;
1)
omitted if dA-L = L14 is defined in hdEF.
2)
omitted if SES = no is defined in hdEF; omitted if not defined in FdEF
Table 3-- 4 Offline parameter list in the configuring mode oFPA (continued)