3.3.7 Configuring Mode FCon (Switch Functions, Connection)
In the FCon configuring mode all the functions defined in FdEF are connected with each other
and with the inputs or outputs of the output or input functions (software connection). A connec-
tion is established by setting a paired data source (outputs)/data sink (inputs) in dd1/dd2. First
the data source (question) and then the corresponding data sink (answer) is set. The connec-
tion is established on switching to the next question or returning to the configuring preselection
mode after FCon.
If controllers CSE* or CSi* were assigned to the arithmetic blocks h01.F in FdEF, the outputs
of the S-controllers h1.2A (+Δy) or h1.3A (--Δy)are permanently assigned to the question posi-
tions bA05 and bA06, adjustment is not possible.
If controllers CSE* or CSi* were assigned to the arithmetic blocks h02.F in FdEF, the outputs
of the S-controllers h2.2A (Δy) or h2.3A (--Δy)are permanently assigned to the question posi-
tions bA07 and bA08, adjustment is not possible.
If the controllers CSE* or CSi were assigned to the arithmetic blocks h03.F in FdEF, the out-
puts of the S-controllers h3.2A (+Δy) or h3.3A (--Δy) are permanently assigned to the question
positions bA3.1/bA3.2 and bA4.1/bA4.2, adjustment is not possible.
If the controllers CSE* or CSi* were assigned to the arithmetic blocks h04.F in FdEF, the out-
puts of the S-controllers h4.2A (Δy) or h4.3A (--Δy) are permanently assigned to the question
positions bA1.1/bA1.2 and bA2.1/bA2.2, adjustment is not possible.
The data sinks and sources of the arithmetic blocks not defined in FdEF and the input and out-
put functions identified by no in hdEF and the SES are faded out of the answer cycle.
Since only combinations of the same signal types (only analog or only digital) are allowed as
question (sink) and answer (source) pairs, only the corresponding data sources can be set on
dd1 in the answer cycle. This supresses illogical connections.
Every data sink can only be assigned one data source, whereas every source can be con-
nected with as many sinks as you like. The parallel loop of inputs (sinks) is therefore achieved
by connection of the respective inputs with the same output (source). The defaults of the inputs
(Hi, Lo, ncon or numeric values) are transferred to the Fcon mode in the description and can be
changed (overwritten) there if necessary.
D Reactions in FCon if changes have been made in FdEF or hdEF
- Deleting a function with ndEF or no:
The existing connection to the inputs and outputs of the deleted function block is re-
moved and inputs of the other function blocks fed by the output or the outputs of the de-
leted function block are identified by ncon.