Preparing for Operation
36
SIP ART PS2 Manual
A5E00074631-01
.
NOTE
The positioner will be equipped at the factory and delivered complete
with the necessary options at the customer’s request. Options modules
may only be retrofitted by our service technicians.
The positioner must be assembled especially in a moist environment
in such a way as to rule out freezing of the positioner axle at low
ambient temperature.
The operating keys must be covered to prevent liquid getting in.
!
W ARNING
In the combination of components it must be ensured that only
positioners and options modules are combined which are approved for
the respective area of application. This applies especially for safe
operation of the positioner in areas in which the atmosphere is
potentially explosive (zone 1 and 2). The instrument categories (2 and
3) of the instrument itself and those of its options must be observed.
In addition, you must always make sure that no water gets into an open
housing or screw--type gland. This may be the case for example when
the positioner cannot be finally assembled and connected immediately.
It generally applies that the positioner may only be operated with dry
compressed air. Therefore use the normal water traps. An additional
drying unit may even be necessary in extreme cases. This is
particularly important when operating the positioner at low ambient
temperatures. Please set the purge air switch (on the valve block
above the pneumatic terminals) additionally to the “OUT” position.
Use a sufficiently rugged console (e.g. plate thickness > 4 mm with
reinforcements) for rotary actuators and the mounting kit linear
actuator” or integrated connection for linear actuators.
3.3.1 Instructions for using positioners in a wet environment
This information gives you important instructions for the assembly and
operation of the positioner in a wet environment (frequent, heavy rain
and/or prolonged tropical condensation) in which the IP65 degree of
protection is no longer sufficient and especially when there is a danger
that water may freeze.
To prevent water getting into the instrument in normal operation (e.g.
through the exhaust air openings) or the display being poorly legible,
please avoid the unfavorable installation positions illustrated in
figure 3-5.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 6DR5010 Series and is the answer not in the manual?

Siemens SIPART PS2 6DR5010 Series Specifications

General IconGeneral
Enclosure RatingIP66/NEMA 4X
Communication ProtocolHART
Housing MaterialAluminum or stainless steel
TypeElectropneumatic
Input Signal4-20 mA
Supply Pressure1.4 to 7 bar
Stroke Range3 to 130 mm
Temperature Range-40°C to +80°C
Ambient Temperature Range-40°C to +80°C
MountingLinear or rotary actuators
Power Supply4-20 mA loop powered