Operation
89
SIP ART PS2 Manual
A5E00074631-01
.
NOTE
But the monitors of the bottom and top hard stop do not only react to
valve errors. Adjustment of the position feedback is also detected as
an error if the tolerance values are exceeded as a result.
Limit value for monitoring the dead zone adaptation
The automatic adaptation of the dead zone can be monitored with this
value (%). If the dead zone exceeds the set value, the fault message
output (optional) is activated.
Prerequisite for this function is the setting of the parameter“34.DEBA” =
Auto. This monitoring function can be deactivated with the OFF setting
(factory setting).
Preset
Establishing the factory setting and resetting the initialization.
.
NOTE
The positioner must be re--initialized after ”Preset”. All previously de-
termined maintenance parameters are cleared.
54. DEBA
55.PRST

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPART PS2 6DR5010 Series and is the answer not in the manual?

Siemens SIPART PS2 6DR5010 Series Specifications

General IconGeneral
Enclosure RatingIP66/NEMA 4X
Communication ProtocolHART
Housing MaterialAluminum or stainless steel
TypeElectropneumatic
Input Signal4-20 mA
Supply Pressure1.4 to 7 bar
Stroke Range3 to 130 mm
Temperature Range-40°C to +80°C
Ambient Temperature Range-40°C to +80°C
MountingLinear or rotary actuators
Power Supply4-20 mA loop powered

Related product manuals