Installing/mounting
3.3 Pneumatic Connections
Venting Gauge Block Installation Instructions
Hardware Installation Manual, 12/2014, A5E34388399-AD
17
season of the year. Under no circumstances should the dew point, at line pressure, exceed
2°C (35.6°F).
Oil Content The maximum total oil or hydrocarbon content, exclusive of non-condensable,
should not exceed 1 ppm under normal operating conditions.