ETH-BD-2FO
Description Communication module for the transmission of Ethernet protocols via
2 optical interfaces, suitable for Process-bus client, Merging Unit, and
ultrafast GOOSE
Product code P1Z3034
Figure
Connector type 2 x duplex LC
Wavelength λ = 1300 nm
Baud rate 100 Mbit/s
Protocol DIGSI 5 protocol (secure Web service protocol)
IEC 61850 (MMS and GOOSE)
IEC 61850-8-1 (9-2 Client and 9-2 Merging Unit)
IEC 60870-5-104
PROFINET IO
Synchrophasor protocol (IEEE C37.118 – PMU)
You can switch other network services such as HSR, SNMP, RSTP, PRP,
SNTP, and IEEE 1588v2/PTP on and off.
Max. line length 2 km for 62.5 µm/125 µm optical fibers
Transmitter Power Minimum Typical Maximum
50 μm/125 μm, NA
30
= 0.2
-24.0 dBm -21.0 dBm -17.0 dBm
62.5 μm/125 μm, NA
30
= 0.275
-20.0 dBm -17.0 dBm -14.0 dBm
Receiver sensitivity Maximum -12.0 dBm
Minimum -31.0 dBm
Optical budget
Minimum 7.0 dB for 50 μm/125 μm, NA
30
= 0.2
Minimum 11.0 dB for 62.5 μm/125 μm, NA
30
= 0.275
Interface design Corresponds to IEEE 802.3, 100Base-FX
Laser class 1 as per EN 60825-1/-2 With the use of 62.5 μm/125 μm and 50 μm/125 μm optical fibers
i
i
NOTE
The firmware must be updated to version ≥ V7.90 if using the ETH-BD-2FO module. If the module is
connected to a device with a previous version, a hardware failure is reported that disappears with an FW
update to V7.90. As this is not an actual hardware failure, there is no need to send in the device.
The ETH-BD-2FO module offers the possibility of replacing the SFPs (Small Form-Factor Pluggable) delivered by
default for a communication route of up to 2 km by SFPs that can be ordered separately in order to adapt the
interface to different transmission media and longer routes.
11.1.5
30
Numerical Aperture (NA = sin θ [launch angle])
Technical Data
11.1 General Device Data
SIPROTEC 5, Low-Impedance Busbar Protection, Manual 907