SFP with Optical Interface for 24 km, Single Mode
Description SFP for distances up to 24 km when using singlemode optical fibers
Product code P1Z3210
Connector type Duplex LC
Wavelength λ = 1300 nm
Baud rate 100 Mbit/s
Protocol See information for the module ETH-BD-2FO
Max. line length 24 km for 9 µm/125 µm optical fibers
Distance 24 km
Laser class 1 as per EN 60825-1/-2 With the use of 9 µm/125 µm optical fibers
Transmitter Power Minimum Maximum
Transmitter power coupled in
singlemode optical fibers
-15 dBm -8 dBm
Receiver sensitivity -8 dBm -31dBm
Optical budget 16 dB
SFP with Electrical Interface
Description SFP with RJ45 connector, for Ethernet protocols via an electrical inter-
face
Product code P1Z3201
Connector type RJ45
Baud rate 100 Mbit/s
Protocol See information for the module ETH-BD-2FO
Max. line length 20 m with Ethernet patch cable CAT 6 S/FTP, F/FTP, or SF/FTP
Interface design Corresponds to IEEE 802.3, 100Base-TX
Removing SFP Pluggable Transceivers
!
CAUTION
Risk of burns due to high temperatures of the SFP pluggable transceivers
Noncompliance with the safety notes may result in medium or light injuries.
²
The SFP pluggable transceivers can be disconnected and plugged in while in operation. Siemens
recommends switching off the device.
²
Allow the SFP pluggable transceiver to cool as much as possible.
Remove the connecting cables or the dust protection cap that was plugged on in the delivery state from
the SFP pluggable transceiver.
In order to release the interlocking, open the bracket on the SFP pluggable transceiver.
Pull on the bracket in order to pull the SFP pluggable transceiver out of the slot. The removal must be
possible with free movement and without great exertion of force.
Provide the SFP pluggable transceiver with the dust protection cap so that the optics are protected from
contamination.
Technical Data
11.1 General Device Data
908 SIPROTEC 5, Low-Impedance Busbar Protection, Manual
C53000-G5040-C019-C, Edition 04.2021

Other manuals for Siemens Siprotec 5 7SS85

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens Siprotec 5 7SS85 and is the answer not in the manual?

Siemens Siprotec 5 7SS85 Specifications

General IconGeneral
BrandSiemens
ModelSiprotec 5 7SS85
CategoryIndustrial Equipment
LanguageEnglish

Related product manuals