Technical data
7SJ61/62/63 6MD63 – Modbus
C53000-L1840-C001-01
7-2
7.2.1 Connection via the AME module
Connections 9pole D-SUB outlet (ref. to Table 7-2)
Protocol semi-duplex
Max. line length 1000 m / 3300 ft
Insulation level 500 V
AC
Bus termination Integrated, connectable terminating resistors
221 Ohm between A and B
392 Ohm between B and VCC1 as well as A and GND1
Input resistor not terminated
≥
10 kOhm, then bus termination via bus plug with
integrated terminating resistors.
Level Transmitter:
Low: -5 V
≤
U
A-B
≤
-1.5 V
High: +5 V
≥
U
A-B
≥
+1.5 V
Receiver:
Low: U
A-B
≤
-0.2 V
High: U
A-B
≥
+0.2 V
Transmitter and receiver are surge-proof for voltages between A and GND1 as well as
B and GND1 in the range of –7 V...+12 V.
Max. number of modules
at the bus
32
8
Table 7-1 Technical data of the connection via the AME module
Pin RS485 signal Meaning
1 Shield Shield / operational ground
2-
3 A RS485 connection pin A
4 RTS Directions control RTS (TTL level)
5 GND1 Ground to VCC1
6 VCC1 Supply voltage +5V DC (max. 100 mA, supply voltage for terminating resistors)
7-
8 B RS485 connection pin B
9-
Table 7-2 Assignment of the bus connection at the device (D-SUB outlet)
7.2.2 Connection via the AMO module
Connections fibre-optical interface, Rx and Tx, 820 nm, BFOC/2.5
Protocol semi-duplex
Max. line length
•
2000 m / 1.25 miles for glass fibre 62.5/125 µm
•
approx. 2 m for plastic fibre
Optical budget min. 8 dB for glass fibre 62.5/125 µm
Status for “no signal“ light OFF
Table 7-3 Technical data of the connection via the AMO module
8
For exclusive utilisation of
AME
modules at the bus.
This value could be smaller depending on the used Modbus master and further modules at the bus.
If more then 32 devices at the bus are needed, RS485 repeaters which support bit retiming have to be used.