SIPROTEC PROFIBUS-DP - Communication profile
C53000-L1840-B001-03
2.5 Event list via PROFIBUS-DP (Sequence of events recorder)
Attention! 
1. This function was especially developed for application of the bay control unit 
6MD663/6MD664 in conjunction with a substation master S5-155H in a HV DC 
substation (high voltage DC transmission). 
Other PROFIBUS-DP masters must be adapted if the function "Event list via 
PROFIBUS-DP" is to be used (refer to item 4).
2. For the "Event list via PROFIBUS-DP" the following is required:
− PROFIBUS-DP communication module firmware from V03.00.03,
− a mapping file that supports "Event list via PROFIBUS-DP".
3. Please check in the bus mapping  documentation of the SIPROTEC device (ref. 
to page 3) that you are applying whether this device provides an "Event list via 
PROFIBUS-DP".
4. To retrieve and evaluate the annunciations from the event list, the applied PROFI-
BUS-DP master must be programmed/set in accordance with the described 
handshake mechanism (ref. to chap. 2.5.3) and data type definition (ref. to 
chap. 3.9).
The required program sequences must be generated by the user.
5. The "Event list via PROFIBUS-DP" is not identical to the operational event log in 
the SIPROTEC device, but is separately maintained on the communication 
module.