EasyManua.ls Logo

Siemens SITOP SEL1200 8 x 5 A - Page 20

Siemens SITOP SEL1200 8 x 5 A
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description, device design, dimension drawing
2.5 Buttons and selector switches
SITOP SEL1200-1400
20 Equipment Manual, 06.2020, A5E46496083-2-76
Manually switching an output on and off
An individual output can be switched on and switched off using the button
(ON/OFF/RST)
. When the device is delivered, the outputs are manually switched off.
Switching off an output:
For outputs that are switched on, LED
of the particular output is lit green. You can switch
off the output by pressing the assigned button (ON/OFF/RST)
. The LED then flashes
orange (output has been manually switched off).
Switching on an output:
For outputs that have been manually switched off, LED
of the particular output is lit
orange. You can switch on the output by pressing the assigned button (ON/OFF/RST)
.
The LED is then lit green (output is switched on).
Note
An output that has been manually switched
-off can only be manually switched-on again by
manually pressing the button again. It is not possible to switch on an output that has been
manually
switched off using the remote reset signal (RST) .
An output that
has been manually switched off remains saved (latch) even when the supply
voltage is no longer available, and is a manually switched off when the supply voltage
returns.

Related product manuals