59
Ambient conditions
8
6EP4437-7FB00-3DX0
6EP4437-7FB00-3CX0
6EP4438-7FB00-3DX0
6EP4437-7EB00-3DX0
6EP4437-7EB00-3CX0
6EP4438-7EB00-3DX0
Ambient temperature
-25 ... 70 °C for natural convection (self convection)
Tested according to:
EN 60068-2-1 Cold, Ad test
EN 60068-2-2 Dry heat, Bb test
EN 60068-2-78 Humid heat, constant Cab test
EN 60068-2-14 Temperature change, Nb test
Transport and storage temperature -40 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 Cold, Ab test
EN 60068-2-2 Dry heat, Bb test
EN 60068-2-30 Humid heat, cyclic Db test
Humidity class Climatic class 3K3 according to EN 60721, 5 - 95 % no
condensation
Degree of pollution
2
Mechanical stressing in operation
Test according to EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 8.4 Hz
2 g acceleration in the range 8.4 - 150 Hz
Test according to EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms

Questions and Answers: