Description, device design, dimension drawing
2.6 Electronic overload shutdown and reset
SITOP SEL1200-1400
22 Equipment Manual, 06.2020, A5E46496083-2-76
Reset of an electronic overload shutdown via button (ON/OFF/RST) ⑥ and remote reset
(RST) ④
An output that has been shut down due to overload can be reset by pressing the associated
button (ON/OFF/RST)
⑥ (reset).
Figure 2-7 Button and remote reset terminal
The initial situation is an electronic shutdown of individual outputs as a result of an overload
condition. This is signaled using the LED 1-8
⑥ of the particular output.
Lit red Electronic shutdown as a result of an overload; wait time until a reset is possible:
Output ready for a reset; press the button to switch-on the output again.
The reset was carried out, the output was switched-on again.
Procedure to reset an electronic shutdown:
1. After an electronic shutdown (LED of the output is lit red), allow a wait time of 20 seconds
to elapse (LED of the output flashes red).
2. Press the reset button
⑥ of the particular output:
Electronic shutdown was reset, and the output is switched-on again (LED of the output is
lit green).