Parameterizing the SITOP UPS1600
6.2 Switching off the UPS by a user program when the power fails
SITOP UPS1600 under STEP 7 V5
Getting Started,
33
Integrating function block FB160 into a project
1. Open the library, select program folder "UPS1600 library" and open the symbol table
"Symbols_UPS1600".
2. With the mouse key pressed, move over the 4 lines "UPS_Battery_charge_level",
"UPS_Buffer_mode", UPS_New_alarms_pending" and "UPS_Ready_for_buffering", to
select them.
3. Copy the four selected entries into the clipboard.
4. Open the symbol table "Symbols" in your target project.
5. Copy the four lines from the template into the table.