Parameterizing the SITOP UPS1600
6.2 Switching off the UPS by a user program when the power fails
SITOP UPS1600 under STEP 7 V5
Getting Started,
35
Calling function block FB160
Calling the function block within an organization block (OB) is described in the following. In
this case, function block FB160 is called within organization block OB1.
Note
Ensure that the update cycle of the organization block being used has a direct influence on
the update time of the function block.
1. In the "Blocks" folder of your project, open block "Main [OB1]" in the FBD view.