Description, device design, dimension drawing
2.4 Status displays and signaling
Selectivity modules
Manual, 01.2017, C98130-A7579-A1-2-7629
17
SITOP PSE200U
LED and group signaling contact or status output
Signaling
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA51
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA61
Off All LEDs:
No supply voltage
Device powering up: After the device has powered up, the outputs are
switched on, taking into consideration the switch-on delay that has been
set.
Group signal: Inactive Status output
1*
: -
LED, individual output:
Output defective (internal fuse has ruptured)
Group signal: Inactive Status output
1*
: Ci = '0'
Lights
up
green
Normal operation, output is switched on
Group signal: Active Status output
1*
: Ci = '1'
Flash-
es
green
The output current is in the overload range according to the shutdown char-
acteristic (see Chapter SITOP PSE200U (Page 23))
-2BA11, -2BA21, -2BA31, -2BA41:
overload at the output: Output current 101 - 150 % of the response threshold
(for 5 s)
-2BA51, -2BA61:
overload at the output: Output current 101 - 110 % of the response threshold
(for 5 s)
Group signal: Active
Status output
1*
: Ci = '1'
Lights
up red
Output automatically shut down due to overload or external overvoltage > typ.
30 V/100 ms. The output can be switched on again after a typical wait time of
20 s. The wait time still to elapse is saved when switching off the device
and is reactivated after the device has been switched on again.
Group signal: Inactive
Status output
1*
: Ci = '0'
Flash-
es red
Output ready to be reset after an automatic switch off by actuating the button
or remote reset (effective for all outputs that have been automatically
switched off)
Group signal: Inactive Status output
1*
: Ci = '0'
Flash-
es
orange
Output manually switched off using the button: The state is saved when the
device is switched off, and can only be reset again by pressing the up button
again.
Group signal: Active
Status output
1*
: Ci = '0'
Red
running
light
Device overtemperature: The outputs can be switched-on again once the
temperature is in the normal range.
Group signal: Inactive
Status output
1*
: Ci = '0'
Group signaling con-
tact (changeover
contact)
In the "inactive" state, 11-12 are
connected and 11-14 open
-