Description, device design, dimension drawing
2.4 Status displays and signaling
Selectivity modules
Manual, 01.2017, C98130-A7579-A1-2-7629
17
LED ⑧ and group signaling contact or status output ④
6EP1961-2BA11
6EP1961-2BA21
6EP1961-2BA51
6EP1961-2BA31
6EP1961-2BA41
6EP1961-2BA61
Off All LEDs:
• No supply voltage
• Device powering up: After the device has powered up, the outputs are
switched on, taking into consideration the switch-on delay that has been
set.
Group signal: Inactive Status output
1*
: -
LED, individual output:
Output defective (internal fuse has ruptured)
Group signal: Inactive Status output
1*
: Ci = '0'
Lights
up
Normal operation, output is switched on
Group signal: Active Status output
1*
: Ci = '1'
Flash-
es
green
The output current is in the overload range according to the shutdown char-
acteristic (see Chapter SITOP PSE200U (Page 23))
-2BA11, -2BA21, -2BA31, -2BA41:
overload at the output: Output current 101 - 150 % of the response threshold
(for 5 s)
-2BA51, -2BA61:
overload at the output: Output current 101 - 110 % of the response threshold
Output automatically shut down due to overload or external overvoltage > typ.
30 V/100 ms. The output can be switched on again after a typical wait time of
20 s. The wait time still to elapse is saved when switching off the device –
and is reactivated after the device has been switched on again.
Flash-
es red
Output ready to be reset after an automatic switch off by actuating the button
or remote reset (effective for all outputs that have been automatically
Group signal: Inactive Status output
1*
: Ci = '0'
Flash-
es
orange
Output manually switched off using the button: The state is saved when the
device is switched off, and can only be reset again by pressing the up button
Red
running
light
Device overtemperature: The outputs can be switched-on again once the
temperature is in the normal range.
Group signaling con-
tact (changeover
In the "inactive" state, 11-12 are
connected and 11-14 open
-