EasyManua.ls Logo

Siemens SITRANS FXT030 - Page 11

Siemens SITRANS FXT030
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DEVICE DESCRIPTION
2
11
SITRANS FX330
www.siemens.com/flow09/2018 - A5E40861058-AB
Max. permissible product and ambient temperatures with signal converter or
connection box mounted above the flow sensor
Temperature class in °C
Temperature class in °F
Temperature class T6 T5 T4 T3 T2
T
amb
in °C 60 65 60 65 60 65 40 60 65 40 60 65
Nominal size
DN1525 80 65 100 100 135 135
1
200 200
1
165
1
240 200
1
165
1
DN4050 80 65 100 100 135 135
1
200 175
1
150
1
240 175
1
150
1
DN65100 80 65 100 100
1
135
1
130
1
200 150
1
130
1
235
1
150
1
130
1
DN150...300 75 65 100 100 135 135
1
200 185
1
155
1
240 185
1
155
1
1 Permanent service temperature of connecting cable and cable entry min. 80°C
Temperature class T6 T5 T4 T3 T2
T
amb
in °F 140 149 140 149 140 149 104 140 149 104 140 149
Nominal size
DN1525 176 149 212 212 275 275
1
392 392
1
329
1
464 392
1
329
1
DN4050 176 149 212 212 275 275
1
392 347
1
302
1
464 347
1
302
1
DN65100 176 149 212 212
1
275
1
266
1
392 302
1
266
1
455
1
302
1
266
1
DN150...300 167 149 212 212 275 275
1
392 365
1
311
1
464 365
1
311
1
1 Permanent service temperature of connecting cable and cable entry min. 176°F