Pointek ULS200
26 Operating Instructions, 01/2019, A5E32268616-AB
The outputs can be set to function in the desired mode.
Application
Function
Relay 1
Relay 2
High/Low level switch
1
High alarm
Low alarm
High level switch with
two height alarms
2
High alarm
High alarm
Low level switch with
two height alarms
3
Low alarm
Low alarm
High level switch with
loss of echo alarm
4
High alarm
LOE alarm
Low level switch with
loss of echo alarm
5
Low alarm
LOE alarm
Pump down control with
low level alarm
6
Pump down
Low alarm
Pump down control with
high level alarm
7
Pump down
High alarm
Pump up control with
low level alarm
8
Pump up
Low alarm
Pump up control with
high level alarm
9
Pump up
High alarm
Pump down control with
loss of echo alarm
10
Pump down
LOE alarm
Pump up control with
loss of echo alarm
11
Pump up
LOE alarm
Pump up control and
Pump down control
12
Pump down
Pump up
Dual pump down con-
trol
13
Pump down
Pump down
Dual pump up control
14
Pump up
Pump up
*Factory setting
Alarm: the relay de-energizes to set the alarm 'ON'.
Control or pump: the relay energizes to set the device 'ON'.