EasyManua.ls Logo

Siemens SITRANS LVL200E - Wiring Recommendations and Examples

Siemens SITRANS LVL200E
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
MAN-100411
SITRANS LVL200E - Operating Instructions
55328-EN-170712
SW E60Z
+
0,5 g / cm
3
0,7 g / cm
3
4
5
1
2
3
12
Fig. 11: Electronics and terminal compartment
1 Control lamp
2 DIL switch for sensitivity adjustment
3 Ground terminal
4 Connection terminals
5 Processing system or PLC
We recommend connecting SITRANS LVL200E in such a way that
the switching circuit is open when there is a level signal, line break or
failure (safe state).
For connection to a SITRANS SCSC or SITRANS TCSC signal
conditioning instrument dto. Ex, WHG. The sensor is powered by the
connected signal conditioning instrument. Further information is avail-
able in chapter "Technical data", "Ex-technical data" are available in
the supplied "Safety information".
The wiring example is applicable for all suitable signal conditioning
instruments.
The control lamp on SITRANS LVL200E lights in general
red - with covered tuning fork
green - with uncovered tuning fork
Take note of the operating instructions manual of the signal condition-
ing instrument. Suitable signal conditioning instruments are listed in
chapter "Technical data".
IfSITRANSLVL200EisusedinExareasaspartofanoverllprotec-
tion system according to WHG (Water Resources Act), take note of
theregulationsinthesafetyinstructionsandconformitycerticates.If
the instrument with electronics module SWE60Z EX, SWE60Z EX E1
is to be operated directly on the analogue input of a PLC, a suitable
safety barrier should be connected.
Electronics and terminal
compartment
Wiring plan

Other manuals for Siemens SITRANS LVL200E

Related product manuals