Standards and references
4
4.1 IEC 60831 Standard and Reference
Following maximum switching operations per year are acceptable:
PhaseCap Premium up to 7500 switching operations
DeltaCap up to 5000 switching operations
PhaseCap HD and PhiCap up to 5000 switching operations
PhaseCap Compact up to 10000 switching operations
PhaseCap Energy+ up to 15000 switching operations
Before considering a higher number of switching operations, please contact Siemens.
Installation and maintenance instructions for Power Factor Correction (PFC) capacitors
Installation Manual, 05/2022, L1V30884033A 21