2.3 Ambient temperature
The ambient temperature category for most standard types is–40 / D. This means a max.
temperature of 55 °C, an average temperature over 24 hours of 45 °C, and the average
temperature in one year should not exceed 35 °C. The maximum casing temperature of 60 °C
must not be exceeded. Temperature is one of the main stress factors for polypropylene type
capacitors. Temperature has a major in󹪞uence on the useful life expectancy of the capacitor.
WARNING
The use of damaged devices may result in death, serious injury, or property damage.
Capacitors should not be used any longer in case of dents, mechanical or any other kind of
damage.
Check the integrity of discharge resistors before installation.
WARNING
Exceeding the maximum allowed temperature may set safety device out of operation. It
may result in death, serious injury, or property damage.
The maximum allowed temperature must not be exceeded.
DANGER
Hazardous voltage will cause death, serious personal injury, or equipment damage.
Turn o󹪜 and lock out all power supplying this equipment before working on this device.
Safety notes
2.3 Ambient temperature
Installation and maintenance instructions for Power Factor Correction (PFC) capacitors
Installation Manual, 05/2022, L1V30884033A 9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIVACON and is the answer not in the manual?

Siemens SIVACON Specifications

General IconGeneral
TypeLow-voltage switchgear and controlgear assembly
Modular designYes
Form of internal separationUp to Form 4b
StandardsIEC 61439-1/-2
Installation typeFixed or withdrawable

Related product manuals