6 - USE
Max ancient diff. Maximum ageing difference of the heat generators
Installer Value Value
Check phase N/A
Installer Value Value
Check time N/A
Installer Value Value
Stop time N/A
Installer Value Value
Module MaxHH Maximum hours of ageing between the heat generators
Installer Value Value
Sequence change Enable or not the sequence change
Installer Value Value
Mod 1 Work Min. Working minutes of heat generator 1
Installer Min value Min value
Mod 2 Work Min. Working minutes of heat generator 2
Installer Min value Min value
Mod 3 Work Min. Working minutes of heat generator 3
Installer Min value Min value
Mod 4 Work Min. Working minutes of heat generator 4
Installer Min value Min value
Sequence value value value
value
Heat generators switch-on sequence
Installer
DHW Heat generators to be used for DHW
Installer
Mode As set in the Parameters>Outputs rotation>Mode menu
Installer Value Value
Fix rotation The rotation of the 0-10 volt outputs occurs every time set on “interval”
Installer
Interval Time after which the outputs are rotated
Installer Value Value
Base time rotation The rotation of the 0-10 volt outputs occurs after the time “Max ancient diff.”. Whenever a CH request for heat
occurs, the 0-10v outputs rise in sequence giving precedence to those with the least number of working hours
Installer Value Value
Max ancient diff. Maximum ageing difference of the heat generators, after which the rotation begins
Installer Value Value
Check time N/A
Installer Value Value
Stop time N/A
Installer Value Value
Module MaxHH Maximum hours of ageing between the heat generators
Installer Value Value
Sequence change Enable or not the sequence change
Installer Value Value
Mod 1 Work Min. Working minutes of heat generator 1
Installer Min value Min value
Mod 2 Work Min. Working minutes of heat generator 2
Installer Min value Min value
Mod 3 Work Min. Working minutes of heat generator 3
Installer Min value Min value
Mod 4 Work Min Working minutes of heat generator 4
Installer Min value Min value
Sequence value value value
value
Heat generators switch-on sequence
Installer
Solar state
Installer
Solar pump dT On Delta between the solar panel sensor and the solar storage tank sensor, to start the solar pump
Installer Value Value
Solar pump dT On Delta between the solar panel sensor and the solar storage tank sensor, to stop the solar pump
Installer Value Value
Min Temp. Setpoint of the solar panel sesor, below which the solar pump always remains stopped
Installer Value Value
Max Temp. Setpoint of the solar panel sesor, above which the solar pump always remains stopped
Installer Value Value
Max load hyst Loading delta with respect to “Max. Temp” to carry out the anti-stagnation function. Beyond this delta the solar
pump will always remain stopped
Installer Value Value
Antistagn On Temp Solar panel setpoint to start the solar pump as anti-stagnation
Installer Value Value
Antistagn Off Temp Solar panel setpoint to stop the solar pump as anti-stagnation, as an excessive temperature has been
reached and the pump is stopped to prevent it from burning. In this case an alarm is generated “A015
Antistagnation: Alarm”
Installer Value Value