Siemens  TX-I/O™ Module system – Functions and operation  CM110561en_08 
Building Technologies  Digital output functions  2018-10-25 
•  The multistate process value is mapped so that the mapping table specifies one or 
more outputs to be driven. 
•  It is possible to have several active outputs, but only in a fixed combination. 
•  Examples: Enabling additional electrical heating or burner stages 
 
n, n+1, n+2, n+3, n+4, n+5 
 
•  The multistate process value is mapped so that the mapping table specifies one or 
more outputs to be driven. 
•  It is possible to have several active outputs. 
•  Examples: Enabling additional electrical heating or burner stages 
 
 
 
In the case of bus failure, with DC 24 V module supply available, the following backup 
states van be parameterized: 
–  No  (Inactive) (= default) 
–  Value  (Active, Inactive) 
–  Keep  Same value as before the bus failure 
 
Parameterization can be done during runtime. 
 
 
•  The I/O status LEDs indicate the activity of the relays 
•  In the case of an error the module status LED and all the I/O status LEDs assigned 
to the function flash.