39/54 
Siemens  TX-I/O™ Module system – Functions and operation  CM110561en_08 
Building Technologies  Digital output functions  2018-10-25 
Pressing the middle of one of the manual switches assigned to the function 
enables/disables local override. 
When local override is active: 
•  Pressing "+" on one of the I/O points switches the load up one stage.  
Repeated or sustained pressure can be used to switch through several stages until 
the function reaches the highest stage. 
•  Pressing "–" on one of the I/O points switches the load down one stage.  
Repeated or sustained pressure can be used to switch through several stages until 
the function stops at the lowest stage. 
•  The change from one stage to the next occurs only after a delay of 0.3 s.  
This makes it possible to reach a stage directly (e.g. jump from stage 2 to stage 0 
and then to stage 3). 
 Users themselves must know whether switch-off is required before 
switching to another stage. 
•  The Override LED of all I/O points assigned to the function go off briefly while the 
switch is pressed. 
•  The I/O status LEDs light up whenever the relays are active. 
•  Local operation can be disabled in the configuration. 
 
For details, especially in relation to flashing pattern and errors: refer to the section "Dis-
play, operation and diagnostics" in the TX-I/O™ Engineering and installation guide [6].