Siemens VALVEGYR LDU11.523A27 - Leakage Rate Calculation; Leakage Rate Formula and Example

Siemens VALVEGYR LDU11.523A27
21 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9/21
Building Technologies Division CC1N7696en
20.04.2016
Calculation of the leakage rate escaping from a length of pipe
Q
Leck
=
(P
G
- P
W
) x V x 3600
P
atm
x t
Test
Q
leck in dm³/h Permissible leakage rate in dm³ per hour or liters per hour
P
G in mbar Overpressure in pipe section between the valves to be tested, at
the beginning of the test phase
P
W in mbar Overpressure set on pressure switch «DW» (normally set to 50
% of the gas mains pressure)
P
atm in mbar Absolute pressure (1.013 mbar normal pressure)
V in dm³ Volume of test space confined by the valves to be tested, includ-
ing the space in the valves themselves
T
test in s Duration of proving time
P
G = 30 mbar
QLeck =
(30 - 15) x 10.36 x 3600
1013 x 27.5
= 20 l/h
P
W = 15 mbar
P
atm
V
= 1013 mbar
= 10.36 dm³
Any valve leakage rate exceeding 20 l/h causes the LDU11...
to initiate lockout
t
Test = 27.5 s
Note!
Select volume of pipe section (V) between the gas valves to be checked and over-
pressure (PW) set on pressure switch (DW) such that the maximum permissible gas
leakage rate (QLeck) will not exceed the rate specified in the local regulations.
Legend
Example