Connections
32
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
Fig. 15 XC100x-A, connection of detectors and manual triggering devices
The number of detectors which can be connected is determined by dividing the
collective system line connection factor (KLK = 32) by the collective element load
factor (KMK = see table below).
Series of detectors Designation KMK Nb
ALGOREX DO1101A / DO1102A / DO1104A 1 32
DT1101A / DT1102A 1 32
DF1191 / DF1192 6 5
SINTESO FDOOT241-9 / FDOOT241-A9 2 1.25 (*) 16 25
FDF221-9 / FDF241-9 5 6
FDL241-9 10 3
SYNOVA OP320C / OH320C 1 32
HI320C / HI322C 1 32
CERBERUS FD110 series OH110, OP110, HI110, HI112 1 32
(*) Depends on detector index and set of parameters
For Sinteso and Cerberus FD110 series detectors, select an appropriate set of parameters.