Programming
59
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
Navigation in programming
Programming is carried out using the « Silence buzzer » (6), « Reset » (7), « Mode
select » (8), « Led test » (9) keys and the 4-digit display:
- The “Silence buzzer” key (6) allows scrolling the steps ahead, the “Reset” (7)
key scrolling back
- The “Mode select” (8) key allows scrolling the options ahead, the “Led test” (9)
key scrolling back
- Both digits on the left indicate programming step, both digits on the right
indicate options available for this step
Entering / leaving programming
1. Remove the front panel
2. Set the panel to operating access level 2
3. Press and hold down the key « Silence buzzer » (6) then enter the digit
code 1 4 2 4 2 3 2 1 on the keyboard to enter programming:
è “Disable” LED(6) lights up (fixed), « Test » (7), « Fire alarm » (8) and
« Remote transmission » (9) LED light up alternatively, « Operating access »
(10) LED switch off
è the display indicates, for example, « 0130 » (=step 01, option 30)
4. Carry out the modifications, if necessary
5. Press simultaneously keys “1” and “4” to save and leave programming or key
“Reset” (S1) on the XCM1002 mainboard to leave programming without saving.
If no further key is pressed for more than 4 minutes, programming mode is automatically terminated,
with modifications saved.
12.2 Presettings
Sixteen country presettings and a factory presetting are available.
Procedure
1. Remove the front panel
2. Press the « Reset » key (S1) XCM1002 board:
è the display indicates « b » (= system boot) then a few seconds later the
indicator « General fault » (2) flashes slowly
3. During this phase ( 30 seconds), press and hold down keys « 1 » to « 4 » of the
keyboard until « b » disappears:
è the display indicates the presetting number (number between 00 and 16)
è LED « General fault » (2) and « Power supply fault » (3) light up (pulsating
fast)
4. If the appropriate presetting is displayed (see table below), go to point 6, if not,
go to point 5
5. Press as many times as necessary the key « Mode » (8) to select the
appropriate presetting
Step selection
6
7
8
9
Digit A
Digit B
“Reset”
“Silence buzzer”
“Mode select