Connections
38
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
7.6.3 Monitored control output 3
This output is exclusively reserved for the connection of the warning panels.
Operation is defined at programming step 12 (see paragraph 12.6).
Fig. 24 XC100x-A, monitored control output 3 connection
1 Warning panel
2 Control output not used (no EOL required)
7.6.4 Monitored control output 4
This output is exclusively reserved for the connection of the actuator release.
These devices can be either electromagnetic or pyrotechnic actuators. Operation is
defined at programming steps 01, 02 and 13 (see paragraphs 12.3 and 12.6).
Step 01
Opt. 00 .. 72
Step 02
Opt. 02 .. 90 or 99
Step 13
Opt. 01 ou 02
Step 02
Opt. 01
Step 13
Opt. 01 or 02
Step 01
Opt. 00 .. 72
X6 -3
X6-4
-
+
1 n
1 10
OR
+
-
1 2
F1
2 AF
Fig. 25 XC100x-A, monitored control output 4 connection
1 Electromagnetic actuators
2 Pyrotechnic actuators
Electromagnetic actuators
- One or more actuators, connected in parallel, can be connected (see example
at paragraph 7.6 to calculate the maximum number of devices per line as well
as maximum line length).
Pyrotechnic actuators
- 1 to 10 actuators maximum, connected in series, can be connected.
- The table below indicates max. line lengths, in meters, according to cable
section for the Siemens Monopist pyrotechnic actuator :
MONOPIST / code A6E60200462
1 2 3 4 5 6 7 8 9 10
1.5 mm