Connection to Sinteso / Cerberus PRO panels
93
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
9. assign element 2:Output ‘Block autom.” to FDCIO OUT 2 (Relay B)
10. assign element 3:Output ‘Block autom.+manual” to FDCIO OUT 3 (Relay C)
18.2.2 Connection variant 2:
Following XC10 zone messages can be displayed:
- “Exting. discharged”
- “Fault”
- “Exting.pre-alarm”
- “Aut+man ext.OFF XC”
- “Aut.ext.OFF XC”
- “Aut.ext.OFF FC” (XC10 blocked from the Sinteso / Cerberus PRO panel)
Following controls are possible from the Sinteso / Cerberus PRO panel:
- Reset
- Block autom.
Fig. 43 Detectors connected to XC10 control panel – Variant 2
Jumper X14 position (relay contact 5) must be changed from factory setting to the right position (NC
contact)
CAUTION
For this variant, Step 37 option 02 must be selected
Configuration example using FXS engineering tool:
Create an XC10 zone:
1. create an area named “Siemens Training Center”
2. create a section named “Room Spirit 1”
3. under this section
a. create an XC10 Zone named “Extinguishing”