Connection to Sinteso / Cerberus PRO panels
95
Building Technologies A6V10257473_e_en_--
Fire Safety 2015-03-04
- Alarm zone 2
ABCD
IN1 IN2 IN3 IN4
Line +
Line -
Line +
Line -
F3
F6 F5 F4
F2 F1
1
X11
X12
X10X27
1
X9
1
X7X6
1
X5
1
1
1
18 V
FDNet
820 Ω
820 Ω
Relay contact 1: Released (Step 15 Opt. 06)
Relay contact 3: Fault (fail safe mode relay is energized when no faults )
Relay contact 4: Automatic blocked and Manual blocked (Step 18 Opt.17)
Relay contact 2: Fire Alarm (Step 16 Opt. 04)
1234
12345
Control Input 4: Automatic blocked (Step 51 Opt. 02)
Control Input 1: Reset (Step 48 Opt. 01)
Control Input 2: Silence Buzzer (Step 49 Opt. 01)
Control Input 3: Silence/Re-sound sounders (Step 50 Opt. 11)
Relay contact 5: Disabled (Step 19 Opt. 11)
3 x 3K01 Ω
Control inputs
18 V
Relay contacts
X14
X13
1
Fig. 44 Detectors connected to Sinteso / Cerberus PRO panel Variant 3
Configuration example using FXS engineering tool:
Create an XC10 zone:
1. create an area named “Siemens Training Center”
2. create a section named “Room Spirit 1”
3. under this section
a. create an XC10 Zone named “Extinguishing”
b. select “Autom. exting. release blockable from Sinteso / Cerberus PRO
c. select “Show blocking of autom. Exting. release on Sinteso / Cerberus
PRO operating terminal”
d. select “Resetable from Sinteso /Cerberus PRO
e. select “Enable” and configure “Reset time” = 10 s
Assign XC10 zone inputs elements (an FDCIO222 is installed inside the XC10):
4. assign element 1:Input ‘Discharged’ to FDCIO IN1
5. assign element 2:Input ‘Fault’ to FDCIO IN2 and select “Input inverted” in
Hardware tab
6. assign element 3:Input ‘Pre-alarmto FDCIO IN3
7. assign element 4:Input ‘Blocked’ to FDCIO IN14
Assign XC10 zone “Reset” output element:
8. create a fire control group named “Training Center - Room Spirit 1”
9. create a fire control named “XC10 Reset pulse 1”
a. formula: “- - - ALL OR - - -“
b. activation delay: 0s
c. deactivation delay 0s
d. activation timeout: Enable / 3s
e. cause: 1:Output ‘Reset’ XC10 Zone “Extinguishing” activated
f. effect: no effects
10. create a fire control named “XC10 Reset pulse 2”
a. formula: “-1”