6.14.3 EMPTYING operations
Domestic hot water circuit (storage tank):
close the domestic hot water circuit isolation valve (prear-
ranged in installation)
open one or more than one hot water taps and drain the
domestic hot water circuit.
Boiler:
loosen the automatic bleed valve (3)
close the heating circuit isolation valves (8) and (9)
connect a rubber hose to the boiler drain valve (7) and open
it
when it has fully emptied, close the drain valve (7)
close the automatic bleed valve (3).
8 7
5
9
3
Fig. 45