1-8
The 4-Point IDC card provides four Style B (Class B) monitor zones. Each
circuit supports a Disable/Enable capability which can be controlled from the
front panel.
Note: This low-current card does not support 2-wire detectors with
relays. An optional 4-Point IDC Card (high-current) card (Part No.
565-610) does support 2-wire detectors with relays.
The 4-Point NAC/Relay card provides 4 field-configurable output points. The
field wiring connects to an 8-position terminal block. You can configure these
points as either NAC or Auxiliary relay by moving the relay to a different socket
position on the board.
Base Panel Modules, Continued
4-Point IDC Card (low-current)
4-Point NAC/Relay Card