Features
Releasing control using the Simplex
®
4010 Fire
Alarm Control Panel to provide**:
Coverage for up to 10 hazard areas of Automatic
Extinguishing Release and/or Deluge and Preaction
Sprinkler System Release
Releasing Appliance Circuit (RAC) control of
compatible Listed/Approved 24 VDC automatic control
actuators, one per circuit; or two 12 VDC actuators in
series per circuit
RAC provides short circuit supervision to coil
supervision module
Four, 2 A Notification Appliance Circuits (NACs) in the
panel for use with Suppression Release Peripherals (SRP)
Additional actuator circuit control and additional NACs
are available using 4009 IDNet Addressable NAC
Extenders and Suppression Release Peripherals
Audible Escalation of Events:
Temporal or 20 bpm March Time pattern for first
cross-zone alarm
120 bpm March Time pattern to indicate releasing timer
active
On steady to indicate releasing timer expired and
actuator is activated
NOTE: Requires NACs dedicated to conventional horn
control (not SmartSync operation) with strobes
controlled on separate NACs
4009 IDNet NAC Extenders provide:
Up to eight NACs for notification requirements and for
NAC input to Suppression Release Peripherals
Control is via IDNet addressable communications
4090-9005/-9006 Suppression Release Peripheral
with Dual Command Control:
Dual command control requires that both IDNet
communications commands and an activated NAC are
present to initiate the desired release
NAC provides wiring supervision to the actuator
including monitoring of coil continuity
Suppression Release Peripheral control features:
An on-board DC-DC regulator compensates for
voltage drops to the peripheral and ensures proper
control circuit voltage over a wide operating range
Provides a single RAC for control of actuators for up
to 1 A using a 2 A NAC input
Related system components:
4010 Series control panel with Releasing Appliqué
Dedicated NAC output from 4010 or NAC Extender
Coil supervision module, one per RAC
Maintenance Switch, one per RAC
Abort Switch connected via an addressable interface
module
UL listed to Standard 864
Agent
source
Agent
discharge
path
Actuator Control Circuit
Actuator
Maintenance
Disconnect Switch
(with indicator lamp)
Coil supervisory
module
COIL SUPERVISION MOD ULE (2 AMP) 2081-9046
INSTALLATION INSTRUCTIO NS 574-437 REV
MAINTAIN 1/4" SEPARAT ION
BETWEEN POWER LIMITED
(RED/BLK) AND NONP OWER
LIMITED (YEL/BLK) WIRING
RED
NAC+
NAC-
BLK
DATE CODE: 519-958
YEL
BLK
S
SIMPLEX TIME RECORDER CO. GARDNER MA. USA
FIRE
RELEASING
DEVICE
Dedicated
NAC circuit
IDNet
communications
Addressable devices
MANUAL
RELEASE
Release
appliance circuit
FIRE ALARM
CONTROL
DISCONNECT
POWER BEFORE
SERVICING
CAUTION
** SYSTEM IS NORMAL **
12:02:15pm Mon 8-Mar-99
SUPV
ACK
SYSTEM
SUPERVISORY
ALARM
ACK
FIRE
ALARM
TROUBLE
ACK
SYSTEM
TROUBLE
ALARM
SILENCE
ALARM
SILENCED
SYSTEM
RESET
AC
POWER
SUPPRESSION RELEASE PANEL
CAUTION: This Control Unit has been arranged for releasing
service. Dis abl e al l rel eas in g devi ce ci rc uit s pri or t o servi ci ng.
4010 Control Panel with
Suppression Release Appliqué
Suppression
Release Peripheral
-
I
D
N
E
T
I
N
+
+
I
D
N
E
T
I
N
-
PUSH AND HOLD
FIRE SUPPRESSION
SYSTEM ABORT
NORMAL
DISC.
/
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
0
1
Power for
indicator lamp
(if required)
4010 Series Releasing Control Typical Block Diagram
Introduction
The 4010 series fire alarm control panel is capable of
controlling actuators for use in automatic extinguishing,
and deluge or preaction releasing systems. IDNet
addressable communications are used to monitor initiating
devices, and for control of 4009 IDNet NAC extenders
and Suppression Release Peripherals. Releasing system
logic is implemented within the 4010 control panel as
required for the local application.
* 4010 Releasing Control has been approved by the California State Fire Marshal (CSFM)
pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM
Listings 7170-0026:226 and 7300-0026:313 for allowable values and/or conditions
concerning material presented in this document. Accepted for use – City of New York
Department of Buildings – MEA35-93E. Additional listings may be applicable; contact
your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
** This document describes features available with 4010 software revision 3.01 or higher.
Refer to data sheet S4010-0001 for model 4010 control panel details including IDNet
communications information.
Releasing Control Fire Alarm Systems
UL, ULC, CSFM Listed; FM Approved; Releasing Control Systems Reference for the
MEA (NYC) Acceptance* 4010 Fire Alarm Control Panel
S4010-0003-5 6/2013