6. Press the <ENTER> key on the Display/Action keypad. If the test is successful, the following
message displays.
_______________________________________________________________________________
A TrueNAC status report can be generated by the panel with the completion of the TrueNAC
Voltage Drop Test.
Sample reports are shown below.
Example of a successful single-channel test:
-----------------------------------------------------------------
Service Port Page 1
Report 6: TrueAlert Device Status Report 10:23:45am WED 07-FEB-07
-----------------------------------------------------------------
TPS 3
SLC 1
POINT ID CUSTOM LABEL TEST RESULT
--------- ---------------------------------------- --------------
T3-1-1 Cafeteria East PASSED
T3-1-2 Cafeteria West PASSED
T3-1-3 Main Lobby PASSED
T3-1-4 Library East PASSED
T3-1-5 Library West PASSED
NOMINAL CURRENT (A): 1.34
WORST_CASE CURRENT (A): 1.97
WORST_CASE VOLTAGE ABOVE/BELOW THRESHOLD (V): 0.9
SLC HAS NOT PASSED UNLESS ALL DEVICES ARE MARKED AS PASSED
---------------------------------------------------------------
_______________________________________________________________________________
Continued on next page
TrueNAC Voltage Drop Test,
Continued
116B
Testing each
TrueAlert Power
Supply’s SLC
117B
The TrueNAC Report
118B
TrueNAC Report
Samples
TPS CARD: X Channel: X
TrueNAC TEST COMPLETED