8-10
Example of a failed single-channel test:
-----------------------------------------------------------------
Service Port Page 1
Report 6: TrueAlert Device Status Report 10:23:45am WED 07-FEB-07
-----------------------------------------------------------------
TPS 3
SLC 1
POINT ID CUSTOM LABEL TEST RESULT
--------- --------------------------------- --------------
T3-1-1 Cafeteria East PASSED
T3-1-2 Cafeteria West PASSED
T3-1-3 Main Lobby PASSED
T3-1-4 Library East PASSED
T3-1-5 Library West FAILED -0.4
T3-1-6 Electrical West FAILED -0.6
NOMINAL CURRENT (A): 1.34
WORST_CASE CURRENT (A): 1.97
WORST_CASE VOLTAGE ABOVE/BELOW THRESHOLD (V): -0.6
SLC HAS NOT PASSED UNLESS ALL DEVICES ARE MARKED AS PASSED
-----------------------------------------------------------------
Example of a successful test with an old HW version for TPS 3:
-----------------------------------------------------------------
Service Port Page 1
Report 6: TrueAlert Device Status Report 10:23:45am WED 07-FEB-07
TPS 3
SLC 1
POINT ID CUSTOM LABEL TEST RESULT
--------- --------------------------------- ---------------------
T3-1-1 Cafeteria East PASSED
T3-1-2 Cafeteria West PASSED
T3-1-3 Main Lobby PASSED
T3-1-4 Library East PASSED
T3-1-5 Library West PASSED
NOMINAL CURRENT (A): 1.34
WORST_CASE CURRENT (A): 1.97
WORST_CASE VOLTAGE ABOVE/BELOW THRESHOLD (V): 0.8
WARNING: OLD VERSION OF TPS HARDWARE USED, RESULTS MAY HAVE
GREATER VARIATIONS THAN EXPECTED
SLC HAS NOT PASSED UNLESS ALL DEVICES ARE MARKED AS PASSED
-----------------------------------------------------------------